CABLE SUPPORT SYSTEM

Photographic records of actual deviations identified during Electrical & ELV construction reviews.

Projects and construction participants are anonymised.

PHOTO RECORD / FACT

Electrical systems

EL-026 / CABLE SUPPORT SYSTEM

PRIORITY / MAJOR

OBSERVED

The cable support system in the recorded area is not secured. The cable tray cover has not been installed.

RISK

Cable support components may move, exert mechanical loads on the installed cable lines, and reduce their protection against external influences.

WHAT TO CHECK

The design solution, fixing method and spacing for the cable support system, the requirement for a tray cover in this area, and the condition of the installed cables.

RECOMMENDED ACTION

Secure the cable support system as specified in the design and install the tray cover in accordance with the adopted design solution.