PHOTO RECORD / FACT
Electrical systems
EL-024 / CABLE LINES / FLOOR SLAB
PRIORITY / MAJOR
OBSERVED
A chase has been cut into a hollow-core floor slab to install a cable line.
RISK
Intervention in the floor slab without a confirmed design solution may affect its structural characteristics.
WHAT TO CHECK
The working documentation, location and depth of the chase, slab construction, and acceptability of this cable routing method. Obtain a structural engineer’s assessment where necessary.
RECOMMENDED ACTION
Before continuing work in this area, verify the acceptability of the chase against the design and structural documentation. If no solution is specified, agree further action with the designer/structural engineer.
PRIORITY / MAJOR